OSHA electrical safety-related work practices in general industry (29 CFR 1910 Subpart S, 1910.331-1910.335): deenergizing, qualified persons, lockout and verification, overhead lines, conductive items, working space, training and alerting techniques. Free practice quiz with instant feedback; every explanation cites the 29 CFR paragraph it is based on. Independent review material: not affiliated with or endorsed by OSHA, not an OSHA Outreach (10/30-hour) exam, and it does not replace the training and evaluation your employer must provide.

Jetzt üben

Die Fragen des Quiz

Frage 1 · Einfachauswahl · 90 s · 1 Pkt.

Under OSHA's electrical work practice rules, what is the default for live parts an employee may be exposed to?

  • Work on them live, with rubber gloves
  • Cover them with electrical tape and carry on working
  • Work on them only during the night shift
  • Deenergize them before work on or near them

Frage 2 · Einfachauswahl · 90 s · 1 Pkt.

Which reason does OSHA accept for NOT deenergizing before work?

  • The job will take less than ten minutes
  • Deenergizing would delay an urgent production order for a customer
  • Deenergizing would shut down life support equipment
  • The worker has done this job many times

Frage 3 · Einfachauswahl · 90 s · 1 Pkt.

Who may work on electric circuit parts that have not been deenergized?

  • Only qualified persons
  • Any trained employee
  • Any supervisor on site
  • Anyone with insulated tools

Frage 4 · Mehrfachauswahl · 90 s · 1 Pkt.

What must a qualified person be trained in, at a minimum? Choose the 3 correct answers.

  • Distinguishing exposed live parts from other parts
  • Determining the nominal voltage of exposed live parts
  • The clearance distances and their voltages
  • Designing a new building's wiring layout

Frage 5 · Wahr / Falsch · 90 s · 1 Pkt.

A push button or selector switch may be used as the only means of deenergizing equipment before work.

  • True
  • False

Frage 6 · Einfachauswahl · 90 s · 1 Pkt.

Before deenergized equipment can be worked as deenergized, what must a qualified person do?

  • Wait at least 30 minutes after switching off
  • Use test equipment to verify the parts are deenergized
  • Ask the operator whether the machine is off
  • Check that the indicator light on the control panel has gone off

Frage 7 · Einfachauswahl · 90 s · 1 Pkt.

What should happen to stored electric energy, such as in capacitors, before work?

  • Nothing, it drains away by itself in time
  • It is released: capacitors discharged and grounded
  • It is measured and the reading written on the lockout tag
  • It is left alone if the panel door is closed

Frage 8 · Einfachauswahl · 90 s · 1 Pkt.

When may a lock be placed without a tag on electrical equipment?

  • Whenever the job is expected to take less than one full shift
  • Never: OSHA always requires both a lock and a tag
  • When the worker is the only person on site that day
  • One circuit, within the shift, with familiar employees

Frage 9 · Einfachauswahl · 90 s · 1 Pkt.

How close may an unqualified person, or the longest conductive object they hold, come to an unguarded overhead line of 50 kV or less?

  • Not closer than 3 feet
  • Not closer than 6 feet
  • Not closer than 10 feet
  • Not closer than 20 feet

Frage 10 · Wahr / Falsch · 90 s · 1 Pkt.

Portable ladders used where they could contact exposed energized parts must have nonconductive siderails.

  • True
  • False

Frage 11 · Mehrfachauswahl · 90 s · 1 Pkt.

Which items may not be worn if they could contact exposed energized parts, unless made nonconductive? Choose the 3 correct answers.

  • Rings
  • Watch bands
  • Metal headgear
  • Cotton work gloves

Frage 12 · Einfachauswahl · 90 s · 1 Pkt.

What may the working space in front of electric equipment be used for?

  • Storing spare parts
  • Parking pallet jacks
  • Nothing but access and work
  • Keeping cleaning carts and ladders

Frage 13 · Einfachauswahl · 90 s · 1 Pkt.

What does OSHA say about the type of electrical safety training?

  • It must be an online course with a final exam
  • Classroom or on-the-job, scaled to the risk
  • It must be delivered by an OSHA inspector
  • One video is enough for every employee

Frage 14 · Einfachauswahl · 90 s · 1 Pkt.

Where signs and barricades do not give enough warning around exposed energized parts, what must be used?

  • A louder alarm bell installed on the panel
  • A longer written procedure for the job
  • A second lock and a tag on the main disconnect switch
  • An attendant stationed to warn and protect employees